SPCC secondary containment calculator for a rectangular berm
Check a flat, rectangular berm around stationary aboveground bulk oil storage. Compare measured space with the largest tank release plus rain, and see the gallons short or left over. This is not the sizing test for a transfer rack or production site.
Is gross berm volume enough?
Compare the largest tank release with the usable space after obstructions, standing liquid and the design rainfall. Use the measured geometry below for a rectangular enclosure; EPA also provides worksheets for other configurations.
EPA — Secondary containment worksheetsWorksheet
Your entries are calculated in this browser, not sent to CleanPermit. Print the result if you need a copy.
Your worksheet result
Worked example
A 20 × 15 ft berm with 2 ft of usable height has about 4,488 gal gross. Subtract 40 ft³ of obstructions, 100 gal of standing water and 3 in of rain over 300 ft²: about 3,528 gal remains for a 3,500 gal release.
See the result for the example inputs
- Volume margin: 28.052 US gal beyond the entered release and rainfall. Verify the berm, drainage controls and assumptions in the field.
- Gross: 20 ft × 15 ft × 2 ft = 600 ft³ = 4,488.312 US gal. Less 299.221 gal displacement and 100 gal standing liquid leaves 4,089.091 gal before rain.
- Rain reserve: 3 in ÷ 12 × 300 ft² × 7.481 gal/ft³ ≈ 561.039 US gal. Available for oil: 3,528.052 US gal; largest tank: 3,500 US gal.
- Required gross space: 3,500 gal oil + 561.039 gal rain + 299.221 gal displaced + 100 gal standing liquid = 4,460.26 US gal. Measured gross space: 4,488.312 US gal.
- After the full tank release, space remains for about 3.15 in of rain over the entered catchment (not wall height). Compare with the documented storm depth of 3 in.
- Assumes vertical sides, a flat floor, no leakage or pumping credit, and 1 ft³ = 1,728/231 US gal. Use site-specific engineering for sloped floors, irregular walls or connected cells. This is a volume check, not design certification.
Guides for this worksheet
Subtract what occupies space inside a berm
Length × width × wall height is gross space. Water and solids already inside share that space with a release. Count the volume of surviving equipment below the overflow elevation, not the nameplate capacity of every tank in the enclosure.
Open guide Guide / Oil storage & SPCCIs 110% containment always enough?
No. For stationary bulk oil storage under §112.8(c)(2), or animal fats and vegetable oils under §112.12(c)(2), the federal test is the entire capacity of the largest single container plus sufficient freeboard for precipitation. Ten percent is not a universal federal rain allowance or a substitute for checking the actual basin.
Open guide Guide / Oil storage & SPCCTurn a rainfall depth into a freeboard reserve
Freeboard is capacity kept available for precipitation, not an arbitrary strip of unused wall. Storm depth in inches divided by 12, multiplied by contributing square feet, gives cubic feet of water. Multiply by about 7.48052 for US gallons.