CleanPermit
Guide / Oil storage & SPCC

Why farms need a separate SPCC screen

A farm under §112.2 is a tract devoted to producing crops or raising animals (including fish) that produced and sold, or normally would have produced and sold, at least $1,000 in agricultural products during a year. WRRDA §1049 changes the aboveground capacity and certification decisions for these operations.

How to approach it

  1. Map each parcel and identify its tanks. For the farm aggregate, §1049(c)(1) excludes individual containers of 1,000 gal or less on separate parcels and containers holding FDA-approved livestock-feed ingredients. The separate container-level exception in §1049(c)(2) also tests a 2,500 gal parcel aggregate; do not treat every separate parcel as wholly exempt.
  2. Under the published farm thresholds, aggregate below 2,500 US gal is exempt; over 2,500 but under 6,000 gal with no reportable history also screens exempt. At exactly 2,500 or 6,000 gal, get EPA regional confirmation because the statute uses strict inequalities. Do not substitute the ordinary 1,320 gal cutoff.
  3. Above 6,000 but below 20,000 gal, with no tank over 10,000 gal and no reportable history, self-certification may be available. Where a plan is required, a tank over 10,000 gal, aggregate at least 20,000 gal, or reportable history points to a PE. Verify history against the amended statute, not an older fact sheet.

Worked example

A qualifying orchard has two 7,500 gal tanks on the main tract. With a route to water, no counted buried storage and no qualifying discharge history, its 15,000 gal aboveground total can fit the farm self-certification path. That does not make it an Appendix G Tier I facility.

Next step

Retain the farm-status basis, parcel inventory and discharge review. For mixed facilities, uncertain parcels or exact boundaries, confirm the path with the EPA region before signing.

Next on this task

Use the worksheet

All oil storage & spcc resources →